What Is Valve Cv? Flow Coefficient, Kv and a Liquid Sizing Example

VantaValve Team   ·   Published November 7, 2026   ·   4 min read

Engineering resources

What Is Valve Cv? Flow Coefficient, Kv and a Liquid Sizing Example

Valve Cv describes flow capacity using a defined relationship between flow and pressure drop.

Home / Engineering Resources

Three Piece Trunnion Mounted Ball Valve (DBB Ball Valve), Class 150LB
Reference valve image: Shinjo Valve. Final configuration confirmed with quotation.

Valve Cv describes flow capacity using a defined relationship between flow and pressure drop. In US customary units, Cv corresponds to the US gallons per minute of water passing through a valve at a one-psi differential under the reference conditions. It is a capacity coefficient, not a pressure rating or a connection size.

A quoted rated Cv commonly describes the fully open valve. A control valve also has a relationship between travel and flow coefficient, so the available Cv at a partly open position can be much smaller. Belimo explains the basic water-flow definition and liquid calculation in its engineering introduction. Belimo Cv guide.

The simple liquid relationship

For a simplified non-choked, turbulent liquid calculation:

Cv = Q × √(SG / ΔP)

Here Q is flow in US gallons per minute, SG is the liquid’s specific gravity relative to water, and ΔP is the differential pressure across the valve in psi. Use the pressure difference across the valve, not the upstream gauge pressure alone.

This relationship is a starting point for an appropriate liquid case. It does not replace the corrections needed for viscous flow, attached fittings, cavitation, flashing or choked conditions. Gas and steam require different sizing treatment. Mixing their conditions into this liquid equation does not produce a valid selection.

Worked example with explicit assumptions

Assume water with SG = 1, a required flow of 24 US gpm and an available valve differential of 4 psi. Also assume the simplified liquid relationship applies and no piping correction is needed for this demonstration.

Cv = 24 × √(1 / 4) = 12.

The result is the flow coefficient required at that operating point. It is not an instruction to buy any valve labelled Cv 12. A modulating valve needs a usable travel range at minimum, normal and maximum duty. Its shutoff differential, actuator capability, materials and pressure-temperature limits also need review.

As a second check, if the same flow had only 1 psi available across the valve, the required coefficient would be 24. This illustrates why upstream pressure alone cannot select a valve: the pressure budget assigned to the valve changes the required capacity.

Cv and Kv use different units

Kv uses cubic metres per hour and a pressure difference expressed in bar for the corresponding water-based convention. The approximate conversions are Cv = 1.156 × Kv and Kv = 0.865 × Cv. Rounding is appropriate for communication; final sizing should use the manufacturer’s calculation method and input units.

For the illustrative Cv of 12, Kv is approximately 10.38. This is a unit conversion of capacity, not a new operating point. Do not combine flow in cubic metres per hour with pressure in psi in either simplified formula unless the equation explicitly includes the conversion factors.

Why oversizing can create control problems

A very large rated coefficient may force a control valve to operate near its closed position during normal flow. Small travel changes can then have a disproportionate effect on the process. Evaluate the flow characteristic and predicted operating travel, rather than selecting the largest coefficient that fits the pipe.

Prepare minimum, normal and maximum flow cases, with corresponding inlet and outlet pressures and fluid temperatures. Include density, viscosity and vapour-pressure information where required. The supplier can then assess both capacity and the conditions that the simple equation leaves out.

Is Cv the same as valve diameter? No. Different constructions at the same nominal size can have different coefficients.

Does higher Cv mean a higher pressure rating? No. Flow capacity and allowable pressure are separate specifications.

See control valves for the relevant product family. Submit the operating cases together so that the selection covers the process range, not one isolated flow value.